The TMP 3-Way Mixing Panel’s primary application is as a single zone mixing device where there are no flow requirements in the primary loop.
Intended to be used with DHW tanks as a heat source, the PLC is programmed with a 24hr timer for potable applications. When not used with a DHW tank as a heat source, secondary zoning downstream of the panel is possible.
A DHW priority option for these panels is not available.
These panels can also be used as subpanels to provide additional mixed temperature loops.
Sequence of operation:
- When the thermostat calls for heat, its internal 24V contacts close, the auxiliary terminals close, and the pump turns on.
- As the pump moves fluid through the panel the thermostatic mixing valve adjusts the fluid temperature based on the user settings.
- When the requirements of the thermostat are met, the internal contacts of the thermostat open, the auxiliary contacts open, and the pump stops.
- The pump is activated once every 24 hours, for 15 minutes, to ensure that potable water in the piping is not stagnant.
California Proposition 65 WARNING
Thumbnail |
Stk# |
Title |
Publication Date |
Size |
Download |
Instructions |
|
L6TMP000 |
TMP040/070 Panel Installation, Operation and Maintenance Manual (Instructions) |
2019-10-07 |
10.49 MB |
Download |
Submittal |
|
SUBTMP000 |
TMP - 3-Way Mixing Panel Submittal |
2015-10-06 |
1.42 MB |
Download |
TMP040/TMP070
Description |
Mechanical |
Electrical Detail |
Electrical Rough-in |
TMP Panel Schematic - General |
SCH-TMP-M001
Download:
PDF | Visio |
SCH-TMP-E001
Download:
PDF | Visio |
SCH-MRIB-R001
Download:
PDF | Visio |